The V1000 is a world-class compact current vector drive that defines a new world standard. Demands for efficient production and better maintainability are on the rise, spurred by global competition.
Other features of the new drive include an extensive power range from fractional to 18,5 kW (up to 4 kW in 230 V single-phase), dual CPUs with a speed scan cycle of 2 ms, embedded Modbus communication up to 115 Kbps, powerful open loop current vector control, programming function block diagrams, below normal panel usage with side-by-side mounting and split personality 'normal duty' and 'heavy duty' ratings (constant/variable torque).
Peformance Features
- Ratings:1/8 to 5 HP at 240 VAC 1-ph
1/8 to 25 HP (ND) at 240 VAC 1/2 to 25 HP (ND) at 480 VAC
- Overload Capacity:
150% for 1 min. (HD) 120% for 60 Sec. (ND)
- DC injection braking, ramp to stop
- Electronic reversing
- Adjustable accel/decel: 0.01 to 6000 seconds
- Controlled speed range:
40:1(1) 100:1(2)
- Speed Regulation
± 0.5 to 1% with slip compensation(1) ± 0.2%(2)
- Control Methods:
V/f Control, Open loop Current Vector Control, PM Open Loop Current Vector Control, Simple closed loop speed control
- Displacement power factor: 0.98
- Output frequency: .1 to 400 Hz
- Frequency resolution: 0.01 Hz with digital reference, 0.06 / 60 Hz with analog reference
- Frequency accuracy:
0.01% with digital command 0.5% with analog command
- Volts / hertz ratio: infinitely adjustable pattern
- DC Injection braking: adjustable amplitude, duration, current limited
- Torque boost: full range, auto
- Power loss ride-thru: 0.5 sec.
- Speed search
- Auto restart
- Electronic Reversing
- 3 Critical frequency rejection settings
- Slip Compensation
- Energy Savings Function
- Enhanced PID with loss of feedback function
Protective Features
- Current limit, stall prevention during accel, decel, and run
- Motor and drive overload
- Over voltage
- Instantaneous over current
- Short circuit
- Under voltage
- Heatsink overheat
- Ground fault protection
- Over/under torque
Design Features
- Dual microprocessor logic
- Digital keypad operator, 5 Digits
- LED status display
- Copy Keypad Function
- Remote Mount Keypad Capability
- RJ45 Style Digital Operator Connector
- 7 multi-function digital inputs
- 3 multi-function digital outputs
- Hardwire baseblock (EN954-1 Cat.3)
- Programmable form C output contact for customer use:
1A at 250 VAC or 30 VDC
- 24 VDC control logic compatible with sourcing or sinking outputs (PNP or NPN)
- Carrier frequency: 15 kHz max; swing PWM
- 16 multi-speed settings plus jog speed
- 2 Remote speed references:
0-10 VDC (20 kohms) or isolated 4-20 mA (250 ohms)
- Signal follower: bias and gain
- 2 programmable open collector outputs
- Analog monitor output:
0-10 VDC proportional to output frequency or output current
- Approximately 400 parameters
- Digital pulse train input (33 kHz max.)
- Cooling fan controlled by drive run/stop
- RS-485/RS-422 MODBUS 115 kbps
- UL and cUL listed; CE marked
- UL recognized electronic overload
- MTBF: exceeds 28 years
- Dynamic Braking Transistor
- NEMA 1 enclosure
- Side by side mounting
- Application Presets
- Maintenance monitors
Service Conditions
- Ambient service temperature:
-10° to 40°C (14° to 105°F) Nema 1
- Ambient storage temperature:
-20° to 60°C (-4° to 140°F)
- Humidity: to 95% non-condensing
- Altitude: to 3300 ft; higher by derating
- Service factor: 1.0
- Input voltage: -15% to +10%
200 to 240 VAC, 380 to 480 VAC
- Input frequency:+/-5%; 50/60 Hz
- Phase sequence insensitive
|
|
REV DATE: 2/16/2009
©2024 SCR Controls, Inc. 3479 Gribble Rd., Matthews, NC 28104 PO Box 2368, Indian Trail, NC 28079 email:
|
|
This sight is viewed best viewed with the latest versions of
Edge and Chrome. |
A. Manufactured items:
MELLTRUM (SPECTRUM REPLACEMENT) ES100A ES125A ES150A ES150ARG ES200A ES200ARG ES222 ES2300RG ES2600RG ES2700 2400-8000 2400-8001W 2450-8000W
2450-8001W 2450-8010W 2450-8015W
EDDY CURRENT CLUTCH 1235 367 FOCUS 2 FOCUS1 FOCUS 1 REPLACEMENT BOULIGNY MARK ANDY SECO BALDWIN ENKEL CUSTOM AUTOMATION SYSTEMS MULTI DRIVE SYSTEMS ERC REPLACEMENT.
|