MODEL |
VAC |
COIL OHMS |
MODEL 120 |
120 |
8.0 - 35 OHMS |
MODEL 120-8.5 |
120 |
36 - 200 OHMS |
MODEL 120A |
120 |
201 - 800 OHMS |
MODEL 120B |
120 |
801 OHMS & UP |
MODEL 120HP |
120 |
.5 - 7.9 OHMS |
MODEL 240 |
240 |
151 OHMS & UP |
MODEL 240A |
240 |
5 - 35 OHMS |
MODEL 240B |
240 |
36 - 150 OHMS |
MODEL 480 |
480 |
151 OHMS & UP |
MODEL 480 & RC4 |
480 |
40 - 150 OHMS |
Contactor dropout, because of power line brownouts, will be eliminated
when a KnowTrip® is added to the contactor. The KnowTrip® is a
patented device manufactured by SCR Controls, Inc., Matthews, NC,
under license from Duke Energy.
A contactor with the KnowTrip® attached will not drop out until the line
voltage has dropped below 30VAC (All Model 120's). After the contactor
has dropped out, it will not pull in again until the line voltage exceeds
70VAC (All Model 120's). The hysteresis prevents chatter and contactor.
coil burnout.
|
SPECIFICATIONS:
MODEL |
COIL OHMS |
DROP OUT |
PULL IN |
DIMENSIONS |
Model 120HP |
.5 - 7.9 ohms |
30vac |
70vac |
4.6" x 6.2" x 2.3" |
Model 120 |
8.0 - 35 ohms |
30vac |
70vac |
1.75" x 1.15" x .75" |
Model 120-8.5 |
36 - 200 ohms |
30vac |
70vac |
1.75" x 1.15" x .75" |
Model 120A |
201 - 800 ohms |
30vac |
70vac |
1.75" x 1.15" x .75" |
Model 120B |
801 ohms & up |
30vac |
70vac |
1.75" x 1.15" x .75" |
All Model 120's are fully automatic and are rated up to 50°C ambient temperature. |
MODEL |
COIL OHMS |
DROP OUT |
PULL IN |
DIMENSIONS |
Model 240A |
5 - 35 ohms |
70vac |
180vac |
4.6" x 6.2" x 2.3" |
Model 240B |
36 - 150 ohms |
70vac |
180vac |
4.6" x 6.2" x 2.3" |
Model 240 |
151 ohms & up |
70vac |
180vac |
4.6" x 6.2" x 2.3" |
Model 240A and Model 240B are fully automatic. Model 240 is adjusted by setting a pot according to coil ohms. All units are rated up to 50°C ambient temperature. |
MODEL |
COIL OHMS |
DROP OUT |
PULL IN |
DIMENSIONS |
Model 480 & RC4 |
40 - 150 ohms |
125vac |
360vac |
2.0" x 3.0" x 1.4" (Model 480) |
|
|
|
|
2.0" x 3.0" x 1.4" (RC) |
Model 480 |
151 ohms & up |
125vac |
360vac |
2.0" x 3.0" x 1.4" |
All Model 480's are adjustable and are rated up to 50°C ambient temperature. |
INSTALLATION:
- Turn off power and measure the contactor coil resistance.
- Models 120/A/B/HP and 240/A/B skip to step 6.
- MODEL 480 ONLY:
- If your coil resistance is 150 ohms or less you must install the RC4
line suppressor (go to step 4).
- If your coil resistance is more than 150 ohms you do not
need the RC4 (go to step 6).
- Remove incoming power wires A and B (see Figure 1)
from the contactor coil and attach them to the black wires from RC4
(see Figure 3).
- Connect the yellow wires of the RC4 to the yellow wires of the Model 480. Skip to step
7.
- Remove incoming power wires A and B (see Figure 1) from the contactor coil and attach them to the yellow wires of the KnowTrip®
(see Figure 2).
- Connect the red wires from KnowTrip® to the contactor coil.
- Mount in desired location near contactor.
- MODEL 480 AND 240 ONLY: Use a small screwdriver and adjust the potentiometer to match the contactor coils resistance
(see Figure 4). If you do not know the coil resistance leave the potentiometer fully counter clockwise (CCW). The KnowTrip® may not work if it is not adjusted properly. To better set the potentiometer, monitor the contactor to see if it drops out. If it does, increase (CW) the setting 1/8 of a turn at a time until the contactor no longer drops out (DO NOT exceed 3/8 turn past recommend setting).
|
|
Figure 1: Contactor without KnowTrip®
Figure 2: Contactor with KnowTrip®
Figure 3: Contactor with RC4 and KnowTrip®
Figure 4: Coil Resistance Setting
NOTE:
A contactor may have 25% more inrush current when used with a KnowTrip®. This extra current could cause a problem if the contactor is used with a PLC.
WARRANTY:
The KnowTrip® has a one-year warranty on device parts. SCR Controls, Inc. is not responsible for lost production or damage caused by device failure.
|
|
REV DATE: 8/15/2006
©2024 SCR Controls, Inc. 3479 Gribble Rd., Matthews, NC 28104 PO Box 2368, Indian Trail, NC 28079 email:
|
|
This sight is viewed best viewed with the latest versions of
Edge and Chrome. |
A. Manufactured items:
MELLTRUM (SPECTRUM REPLACEMENT) ES100A ES125A ES150A ES150ARG ES200A ES200ARG ES222 ES2300RG ES2600RG ES2700 2400-8000 2400-8001W 2450-8000W
2450-8001W 2450-8010W 2450-8015W
EDDY CURRENT CLUTCH 1235 367 FOCUS 2 FOCUS1 FOCUS 1 REPLACEMENT BOULIGNY MARK ANDY SECO BALDWIN ENKEL CUSTOM AUTOMATION SYSTEMS MULTI DRIVE SYSTEMS ERC REPLACEMENT.
|